XLPE Cable

Dataflex Cables 1100 Volts Three (3) Core Aluminium Conductor; XLPE Insulated & PVC Sheathed.Unarmoured (A2XY) Cables conforming to IS: (Pt-1) Amended upto Date

Nominal Cross Sectional Area
Conductor Aluminium Min No. of wires
Nominal Thickness of insulation
Min. thickness of Inner Sheath
Nominal Thickness of Outer Sheath
Approx. O.D
Max d.c Resistance at 20 Deg C
Approx a.c Resistance at operating Temp 90 Deg C
Current Rating
Short Ckt. Rating for 1 Sec. Duration
Ground
Air
sq.mm
Nos.
mm
mm
mm
mm
ohm/km
ohm/km
Amps
Amps
kAmps
25
6
0.9
0.3
2.0
20
1.20
1.54
95
100
2.35
35
6
0.9
0.3
2.0
22
0.868
1.11
110
125
3.29
50
6
1.0
0.3
2.0
25
0.641
0.820
130
150
4.70
70
12
1.1
0.4
2.2
28
0.443
0.567
160
180
6.58
95
15
1.1
0.4
2.2
32
0.320
0.410
190
220
8.93
120
15
1.2
0.4
2.2
35
0.253
0.324
215
250
11.3
150
15
1.4
0.5
2.4
39
0.206
0.264
245
290
14.1
185
30
1.6
0.5
2.6
43
0.164
0.210
275
330
17.4
240
30
1.7
0.6
2.8
48
0.125
0.160
320
390
22.6
300
30
1.8
0.6
3.0
52
0.100
0.128
360
455
28.2
400
53
2.0
0.7
3.2
59
0.0778
0.0996
410
530
37.6