Dataflex 1100 Volts Single (1) One Core Aluminium Conductor;XLPE Insulated & PVC Sheathed.Unarmoured (A2XY) Cables conforming To IS: (Pt-1) Amended upto date
Nominal Cross-sectional Area |
Conductor Aluminium Min. No. of Wires |
Nominal Thickness of insulation |
Nominal thickness of Outer sheath |
Approx. O.D |
Max. d.c Resistance at 20 Deg C |
Approx. a.c Resistance at operating Temp.90 Deg C |
Current Rating(3 cables in touching) |
Short Ckt Rating for 1 Second Duration |
|
Ground |
Air |
||||||||
sq.mm |
Nos. |
mm |
mm |
mm |
ohm/km |
ohm/km |
Amps |
Amps |
Amps |
25 |
6 |
0.9 |
1.8 |
12 |
1.20 |
1.54 |
100 |
105 |
2.35 |
5 |
6 |
0.9 |
1.8 |
13 |
0.868 |
1.11 |
115 |
130 |
3.29 |
50 |
6 |
1.0 |
1.8 |
14 |
0.641 |
0.820 |
140 |
160 |
4.70 |
70 |
12 |
1.1 |
1.8 |
16 |
0.443 |
0.567 |
165 |
190 |
6.58 |
95 |
15 |
1.1 |
1.8 |
18 |
0.320 |
0.410 |
205 |
235 |
8.93 |
120 |
15 |
1.2 |
1.8 |
20 |
0.253 |
0.324 |
225 |
275 |
11.3 |
150 |
15 |
1.4 |
2.0 |
22 |
0.206 |
0.264 |
255 |
315 |
14.1 |
185 |
30 |
1.6 |
2.0 |
24 |
0.164 |
0.210 |
285 |
360 |
17.4 |
240 |
30 |
1.7 |
2.0 |
27 |
0.125 |
0.160 |
330 |
435 |
22.6 |
300 |
30 |
1.8 |
2.0 |
29 |
0.100 |
0.128 |
375 |
505 |
28.2 |
400 |
53 |
2.0 |
2.2 |
33 |
0.0778 |
0.0996 |
425 |
600 |
37.6 |
500 |
53 |
2.2 |
2.2 |
37 |
0.0605 |
0.0774 |
485 |
695 |
47.0 |
630 |
53 |
2.4 |
2.2 |
40 |
0.0469 |
0.0600 |
550 |
815 |
59.2 |
800 |
53 |
2.6 |
2.4 |
45 |
0.0367 |
0.0470 |
625 |
970 |
75.2 |
1000 |
53 |
2.8 |
2.6 |
50 |
0.0291 |
0.0372 |
690 |
1100 |
94.0 |