XLPE Cable

Dataflex Cables 1100 Volts Single(1) Core Aluminium Conductor; XLPE Insulated & PVC Sheathed. Hard Drawn AI Armoured (A2XW(AI)Y) Cables conforming To IS: (Pt-1) Amended upto Date

Nominal Cross-Sectional Area
Conductor Aluminium Min. No. of wires
Nominal thickness of Insulation
Nominal Size of Armour Wire
Min. Thickness of Outer Sheath
Approx. O.D
Max. d.c Resistance at 20 Deg C
approx. a.c Resistance at operating temp.90 Deg C
Current Rating
Short Ckt Rating For 1 sec.Duration
Ground
Air
sq.mm
Nos.
mm
mm
mm
mm
ohm/km
ohm/Km
Amps
Amps
kAmps
25
6
1.2
1.4
1.24
15
1.20
1.54
100
105
2.35
5
6
1.2
1.4
1.24
16
0.868
1.11
115
130
3.29
50
6
1.3
1.4
1.24
18
0.641
0.820
140
160
4.70
70
12
1.4
1.4
1.24
20
0.443
0.567
165
190
6.58
95
15
1.4
1.6
1.4
22
0.320
0.410
205
235
8.93
120
15
1.5
1.6
1.4
23
0.253
0.324
225
275
11.3
150
15
1.7
1.6
1.4
25
0.206
0.264
255
315
14.1
185
30
1.9
1.6
1.4
27
0.164
0.210
285
360
17.4
240
30
2.0
1.6
1.4
30
0.125
0.160
330
435
22.6
300
30
2.1
1.6
1.56
33
0.100
0.128
375
505
28.2
400
53
2.4
2.0
1.56
37
0.0778
0.0996
425
600
37.6
500
53
2.6
2.0
1.56
39
0.0605
0.0774
485
695
47.0
630
53
2.8
2.0
1.72
45
0.0469
0.0600
550
815
59.2
800
53
3.1
2.0
1.88
50
0.0367
0.0470
625
970
75.2
1000
53
3.1
2.5
2.04
55
0.0291
0.0372
690
1100
94.0