Dataflex Cables 1100 Volts Single(1) Core Aluminium Conductor; XLPE Insulated & PVC Sheathed. Hard Drawn AI Armoured (A2XW(AI)Y) Cables conforming To IS: (Pt-1) Amended upto Date
Nominal Cross-Sectional Area |
Conductor Aluminium Min. No. of wires |
Nominal thickness of Insulation |
Nominal Size of Armour Wire |
Min. Thickness of Outer Sheath |
Approx. O.D |
Max. d.c Resistance at 20 Deg C |
approx. a.c Resistance at operating temp.90 Deg C |
Current Rating |
Short Ckt Rating For 1 sec.Duration |
|
Ground |
Air |
|||||||||
sq.mm |
Nos. |
mm |
mm |
mm |
mm |
ohm/km |
ohm/Km |
Amps |
Amps |
kAmps |
25 |
6 |
1.2 |
1.4 |
1.24 |
15 |
1.20 |
1.54 |
100 |
105 |
2.35 |
5 |
6 |
1.2 |
1.4 |
1.24 |
16 |
0.868 |
1.11 |
115 |
130 |
3.29 |
50 |
6 |
1.3 |
1.4 |
1.24 |
18 |
0.641 |
0.820 |
140 |
160 |
4.70 |
70 |
12 |
1.4 |
1.4 |
1.24 |
20 |
0.443 |
0.567 |
165 |
190 |
6.58 |
95 |
15 |
1.4 |
1.6 |
1.4 |
22 |
0.320 |
0.410 |
205 |
235 |
8.93 |
120 |
15 |
1.5 |
1.6 |
1.4 |
23 |
0.253 |
0.324 |
225 |
275 |
11.3 |
150 |
15 |
1.7 |
1.6 |
1.4 |
25 |
0.206 |
0.264 |
255 |
315 |
14.1 |
185 |
30 |
1.9 |
1.6 |
1.4 |
27 |
0.164 |
0.210 |
285 |
360 |
17.4 |
240 |
30 |
2.0 |
1.6 |
1.4 |
30 |
0.125 |
0.160 |
330 |
435 |
22.6 |
300 |
30 |
2.1 |
1.6 |
1.56 |
33 |
0.100 |
0.128 |
375 |
505 |
28.2 |
400 |
53 |
2.4 |
2.0 |
1.56 |
37 |
0.0778 |
0.0996 |
425 |
600 |
37.6 |
500 |
53 |
2.6 |
2.0 |
1.56 |
39 |
0.0605 |
0.0774 |
485 |
695 |
47.0 |
630 |
53 |
2.8 |
2.0 |
1.72 |
45 |
0.0469 |
0.0600 |
550 |
815 |
59.2 |
800 |
53 |
3.1 |
2.0 |
1.88 |
50 |
0.0367 |
0.0470 |
625 |
970 |
75.2 |
1000 |
53 |
3.1 |
2.5 |
2.04 |
55 |
0.0291 |
0.0372 |
690 |
1100 |
94.0 |