Dataflex Cables 1100 Volts Two(2) Core Aluminium Conductor; XLPE Insulated & PVC Sheathed.Armoured (A2XFY) Cables conforming To IS: (Pt-1) Amended upto Date
Nominal Cross-Sectional Area |
Conductor Aluminium Min. No Wires |
Nominal Thickness of Insulation |
Min. Thickness of Inner Sheath |
Nominal Size of Armour Strip |
Min. Thickness of Outer Sheath |
Approx. O. D |
Max. d.c Resistance at 20 Deg C |
approx. a.c Resistance at operating temp.90 Deg C |
Current Rating |
Short Ckt Rating For 1 sec.Duration |
|
Ground |
Air |
||||||||||
25 |
6 |
0.9 |
0.3 |
4x0.8 |
1.4 |
18 |
1.20 |
1.54 |
120 |
100 |
2.35 |
5 |
6 |
0.9 |
0.3 |
4x0.8 |
1.4 |
20 |
0.868 |
1.11 |
147 |
126 |
3.29 |
50 |
6 |
1.0 |
0.3 |
4x0.8 |
1.4 |
22 |
0.641 |
0.820 |
174 |
166 |
4.70 |
70 |
12 |
1.1 |
0.3 |
4x0.8 |
1.56 |
25 |
0.443 |
0.567 |
214 |
199 |
6.58 |
95 |
15 |
1.1 |
0.4 |
4x0.8 |
1.56 |
27 |
0.320 |
0.410 |
250 |
254 |
8.93 |
120 |
15 |
1.2 |
0.4 |
4x0.8 |
1.56 |
30 |
0.253 |
0.324 |
275 |
279 |
11.3 |
150 |
15 |
1.4 |
0.4 |
4x0.8 |
1.72 |
32 |
0.206 |
0.264 |
315 |
322 |
14.1 |
185 |
30 |
1.6 |
0.5 |
4x0.8 |
1.72 |
35 |
0.164 |
0.210 |
369 |
356 |
17.4 |
240 |
30 |
1.7 |
0.5 |
4x0.8 |
1.88 |
40 |
0.125 |
0.160 |
415 |
424 |
22.6 |
300 |
30 |
1.8 |
0.6 |
4x0.8 |
2.04 |
43 |
0.100 |
0.128 |
465 |
481 |
28.2 |
400 |
53 |
2.0 |
0.6 |
4x0.8 |
2.36 |
50 |
0.0778 |
0.0996 |
500 |
555 |
37.6 |